Request a Quote →

Termojel Heating-Cooling Units

Heating and cooling in one cabinet, 5–120 °C

Termojel Heating-Cooling Units Products(2)

What is a Termojel?

A Termojel is a process temperature control unit that combines a chiller and a heater in a single cabinet. A refrigeration circuit with a scroll compressor, a separate chiller water tank and pump, a process water pump and an electric heater share the same housing. The unit holds the process water at the required value between 5 °C and 120 °C: when the mold needs cooling, the refrigeration circuit engages; when it needs heating, the electric heater takes over.

In injection molding this means one device instead of a separate chiller and a separate mold temperature control unit. It is particularly practical on machines without a central cooling line, for molds whose temperature changes often, and in production that runs at both low and medium temperatures.

The units in this category are offered by our group company Oksan; there are two types:

TypeModel rangeCooling capacityHeaterUse
Single circuitHW0306F – HW4036F9.59–129.06 kW6–36 kWOne mold or one process circuit
Dual circuitHW0506S2/F2 – HW2032S4/F415.91–67.14 kW2 × 6 – 2 × 12 kWTwo separate process circuits (for example, the two mold halves)

Common features from the manufacturer's catalog

  • Scroll compressors of European and US origin
  • Adjustable heating power; temperature control range +5 °C to +120 °C
  • Integrated stainless steel piping (less clogging, corrosion resistance)
  • Electrical components: OMRON, SIEMENS, LS, JUMO, SCHNEIDER, ABB
  • Control: microcomputer or PLC (optional); RS485 communication for automated management (optional)
  • Safety protections with fault indication, easy maintenance
  • High-efficiency evaporator and condenser

Why single circuit, why dual circuit?

A single-circuit unit holds the whole mold at one temperature. A dual-circuit unit has two independent process pumps and two heaters, so the two circuits can be set to different temperatures. It is preferred for parts where the fixed and moving mold halves need different temperatures (to balance warpage, for visible surface quality) or when two machines are supplied from one unit.

What to check when selecting

1. Cooling load: the heat to be removed from the mold is found with the mold cooling calculator; the unit's nominal cooling capacity must be above it. 2. Heat-up time: the heater power determines how long the mold and the water in the circuit take to reach operating temperature. 3. 120 °C limit: a Termojel goes up to 120 °C. Materials that need higher mold temperatures (such as PPS and PEEK) require an oil mold temperature control unit. 4. Connection size and pump: the process water flow rate and pressure drop must suit the channel layout of the mold.

Contact our technical support team to work out together which unit is right for you.